|
Controlled Power LLC |
INDEX
| CORPORATE | PRODUCTS | ENGINEERING | SALES | CONTACT
CIRCUIT BREAKERS | SWITCHGEAR | CUSTOM FABRICATION
Switchgear is typically installed in:
Available Types Low voltage switchgear can be applied on distribution systems with:
Static
Trip units are provided on all low voltage circuit breakers.
All circuit breakers are UL listed.
Applicable standards of IEEE and NEMA
Drawout circuit breakers are in accordance with: ANSI C37.13 – Low Voltage AC Power Circuit Breakers Used in Enclosures
Circuit Protection and Reliability CP switchgear provides efficient and safe power distribution and control. All applicable ANSI, NEMA, and IEEE standards are met. Closed-door racking is standard. Mechanical interlocks prevent racking a closed circuit breaker or mismatching a breaker and a compartment. Each compartment is also enclosed with grounded steel barriers. Harmonics-induced trips are avoided with the static trip unit, standard on all circuit breakers. By using RMS current sensing, accurate load protection is provided without causing unnecessary shutdowns or jeopardizing system integrity due to high trip settings. All switchgear is manufactured, assembled, and tested in one location. This assures an integrated fit and high quality. The overall effect is guaranteed reliability. Application Flexibility Circuit breaker sizes are available with ratings from 800A to 5000A. Extended interruption ratings are optional with up to 130kA without fuses and 200kA with fuses. Frames rated up to 2000A can be stacked four high and can include integrally mounted fuses. A single vertical section can accommodate a fused 3200A, 4000A, or 5000A circuit breaker. Three widths of vertical sections are available to simplify planning and design: 22, 30, and 38 inches. The 22 inch and 30 inch sections have a uniform depth of 60 inches, while the 38 inch section is 74 inches deep. Rear extensions are available as needed for additional cabling area. All breaker sizes can be housed in a combination of these sections. Description The
switchgear assembly consists of multiple metal-enclosed,
vertical sections.
Normally the end sections are designed to allow
for installation of future sections.
Each vertical section consists of up to four
individually enclosed breaker or auxiliary compartments.
Compartments are sized to provide uniform height
of each switchgear assembly. Various
components such as circuit breakers, instrumentation
and control equipment, transformers, relays, three-phase
bus work, all internal wiring, connectors, and other
supporting equipment are included in each assembly.
These units can be directly coupled to 480V motor
control centers if desired. In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50ºC. The main bus maximum temperature rise is 65ºC above 40ºC ambient. The temperature rise of the air surrounding the cable connection points is limited to 45ºC above 40ºC ambient. Main and Ground Bus The standard main bus is silver plated copper. The main three-phase horizontal bus is arranged vertically one phase above the other with edge-to-edge alignment to provide high, short circuit strength. An insulated main and vertical bus are optionally available. The main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes continuous current. A neutral bus is furnished when specified, and can be rated 1600, 2000, 3200, or 4000 amperes continuous current. A standard
¼ x 2 inch copper ground bus extends through all sections
and is securely bolted.
A cable lug can be mounted to the ground bus
in each section.
Minimum bus bracing is 65,000 amperes RMS symmetrical.
Higher symmetrical bracings are available based
on the highest breaker short circuit rating in the group. Assembly Construction The
metal-enclosed power switchgear is constructed of preformed,
full-depth, 14 gauge steel sheets bolted together and
reinforced with cross-member braces to form a rigid,
self-supporting compact assembly.
The top and rear plates, and side sheets are
all 14 gauge steel.
When two vertical sections are mounted together,
two sheets of 14 gauge steel separate adjacent circuit
breaker compartments. Bolted
steel-glass polyester compartments housing each power
circuit breaker are mounted in the vertical section
to form the switchgear assembly.
This assembly isolates the circuit breakers from
the bus/cable section and from adjacent circuit breaker
compartments. The bus/cable section includes the main horizontal bus, riser bus, connections from the main bus to each set of primary disconnects, and load side copper run-back bus. The cable lugs are accessible without reaching over the main bus. Grounded metal barriers can be provided to isolate the main bus from the cable connections. Barriers are also available to isolate the incoming line of the main circuit breakers from the main load bus of the switchgear. Control Wiring Standard secondary and control wiring is #14 AWG extra-flexible, stranded copper type SIS. Terminations are made with compression-type, insulated terminals. For devices not having screw-type terminals, locking spade-type lugs are used. Sleeve-type computer generated wire markers are provided as standard on each end of all control wires. Insulation The insulation used in the switchgear is fiberglass-reinforced, polyester material that has high impact strength and low moisture absorption. Other features include high flame retardance, high resistance to chemical fumes, and long life at high temperatures. Circuit Breaker Compartments Typical circuit breaker compartments include primary disconnects, ground disconnect, drawout rails, and associated safety interlocks and secondary disconnects, if appropriate. Compartments for electrically operated circuit breakers include secondary disconnects and control circuit fuses. The pullout fuse holder has a set of clips to store the holder in the fuse block when the circuit is disconnected. Up to three current transformers for metering or relaying can be mounted in each compartment. Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices. A typical compliment of devices includes a breaker control switch with red & green light, ammeter with switch, and test block. Metering and Auxiliary CompartmentsMetering and auxiliary compartments are available to house devices such as voltage transformers, metering, control power transformers, and supervisory devices that do not fit on a normal breaker door. Instrument and Control TransformersVoltage transformers and control power transformers are mounted in auxiliary compartments. These transformers are protected by primary pull-out type current-limiting fuses and secondary fuses. Current transformers are normally mounted on the compartment primary disconnect studs where they are readily accessible. Accessories Each switchgear assembly includes the following standard accessories:
As an optional accessory, a test cabinet is available for indoor use that is wall mounted with necessary equipment for testing electrically operated breakers that have been removed from the breaker compartment. Outdoor SwitchgearCP's outdoor switchgear is enclosed in a weather resistant (NEMA 3R) steel housing. All exterior doors extend below the floor line and re sealed with synthetic rubber gaskets. For protection from snow, rain, and dust, the switchgear rests on a six-inch, formed steel base, which provides rigid support and a tight bottom seal. A heavy duty, coal tar emulsion protective undercoating 1/32 inch thick is applied to the underside for protection against moisture and corrosion. Shielded ventilation housing permit proper air circulation while excluding dust, dirt, and foreign matter. The full-length front doors are hinged and may be padlocked. Rear doors are hinged and secured with captive bolts. A lighted, unobstructive service aisle is provided at the front of the switchgear allowing inspection and maintenance without exposure to the elements. An access door equipped with an emergency bar release is at each end of the aisle. A GFI convenience outlet is included. Climatized substation buildingsAs with all of CP manufactured equipment, low voltage switchgear can be mounted in one of our Power Control Centers and integrated with other power distribution equipment.
INDEX
| CORPORATE | PRODUCTS | ENGINEERING | SALES | CONTACT Copyright © 2000-2005 Controlled Power, LLC.
All Rights Reserved.
|