Controlled Power Corporation

CPC HOME
CPC CORPORATE
CPC PRODUCTS
CPC CIRCUIT BREAKERS
CPC SWITCHGEAR
CPC CUSTOM FAB
CPC ENGINEERING
CPC SALES
CPC CONTACT

Controlled Power LLC
Office: 295 Wetmore Ave. S.E.
Massillon, OH USA 44646
Phone: 330.834.3200
Toll Free: 800.321.0414
Fax: 330.834.3201
Corp HQ:
725 E Harrison St
Corona, CA 92879
Phone: 951-520-1900
Toll-Free: 866-MY-MYERS
Fax: 951-520-1961

sales@controlledpower.com

 
INDEX | CORPORATE | PRODUCTS | ENGINEERING | SALES | CONTACT
CIRCUIT BREAKERS | SWITCHGEAR | CUSTOM FABRICATION

480V   S W I T C H G E A R    T E C H    I N F O


General Description


Low Voltage metal-enclosed switchgear is used in electric power distribution systems for the control and protection of circuits and equipment. The switchgear employs drawout type low voltage power circuit breakers.

Switchgear is typically installed in:

bullet Industrial Plants – for power and lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material-handling equipment drivers.
bullet Utility and Co-generation Facilities – for motor control centers to protect and distribute power to electrical devices such as blowers, compressors, fans, pumps, and motors.
bullet Commercial and Residential Buildings – for protection and distribution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.

Available Types

CP switchgear is available in two types:

Indoor (NEMA 1)
Outdoor (NEMA 3R)

Low voltage switchgear can be applied on distribution systems with:

bullet Three phase, 3- or 4-wire feeders, 50 or 60 Hertz
bullet Voltages of 208, 240, 480, or 600 volts
bullet Currents up to 5000 amperes
bullet The circuit breakers may be either manually or electrically operated, fused or unfused. CP utilizes General Electric circuit breakers and can offer Cutler Hammer, or Siemens air magnetic circuit breakers for an additional cost.

Static Trip units are provided on all low voltage circuit breakers. All circuit breakers are UL listed.

Industry Standards

CP's switchgear with power circuit breakers is designed, tested, and constructed to be in accordance with:

bullet ANSI C37.20.1 – Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear
bullet ANSI C37.50 – Test Procedure for Low Voltage AC Power Circuit Breakers Used in Enclosures
bullet ANSI C37.51 – Conformance Testing of Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies

Applicable standards of IEEE and NEMA

bullet UL 1558 – Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear

Drawout circuit breakers are in accordance with: ANSI C37.13 – Low Voltage AC Power Circuit Breakers Used in Enclosures

bullet ANSI C37.16 – Preferred Ratings, Related Requirements, and Application for Low Voltage Power Circuit Breakers and AC Power Circuit Protectors
bullet ANSI C37.17 – Trip Devices for AC and General Purpose DC Low-Voltage Power Circuit Breakers
bullet UL 1066 – Low Voltage AC & DC Power Circuit Breakers Used in Enclosures

Circuit Protection and Reliability

CP switchgear provides efficient and safe power distribution and control.  All applicable ANSI, NEMA, and IEEE standards are met.

Closed-door racking is standard.  Mechanical interlocks prevent racking a closed circuit breaker or mismatching a breaker and a compartment.  Each compartment is also enclosed with grounded steel barriers.

Harmonics-induced trips are avoided with the static trip unit, standard on all circuit breakers.  By using RMS current sensing, accurate load protection is provided without causing unnecessary shutdowns or jeopardizing system integrity due to high trip settings.

All switchgear is manufactured, assembled, and tested in one location.  This assures an integrated fit and high quality.  The overall effect is guaranteed reliability.

Application Flexibility

Circuit breaker sizes are available with ratings from 800A to 5000A.  Extended interruption ratings are optional with up to 130kA without fuses and 200kA with fuses.

Frames rated up to 2000A can be stacked four high and can include integrally mounted fuses.  A single vertical section can accommodate a fused 3200A, 4000A, or 5000A circuit breaker.  Three widths of vertical sections are available to simplify planning and design: 22, 30, and 38 inches.  The 22 inch and 30 inch sections have a uniform depth of 60 inches, while the 38 inch section is 74 inches deep.  Rear extensions are available as needed for additional cabling area.  All breaker sizes can be housed in a combination of these sections. 

Description

The switchgear assembly consists of multiple metal-enclosed, vertical sections.  Normally the end sections are designed to allow for installation of future sections.  Each vertical section consists of up to four individually enclosed breaker or auxiliary compartments.  Compartments are sized to provide uniform height of each switchgear assembly.

Various components such as circuit breakers, instrumentation and control equipment, transformers, relays, three-phase bus work, all internal wiring, connectors, and other supporting equipment are included in each assembly.  These units can be directly coupled to 480V motor control centers if desired.

In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50ºC.  The main bus maximum temperature rise is 65ºC above 40ºC ambient.  The temperature rise of the air surrounding the cable connection points is limited to 45ºC above 40ºC ambient.

Main and Ground Bus

The standard main bus is silver plated copper.

The main three-phase horizontal bus is arranged vertically one phase above the other with edge-to-edge alignment to provide high, short circuit strength.  An insulated main and vertical bus are optionally available.

The main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes continuous current.  A neutral bus is furnished when specified, and can be rated 1600, 2000, 3200, or 4000 amperes continuous current.

A standard ¼ x 2 inch copper ground bus extends through all sections and is securely bolted.  A cable lug can be mounted to the ground bus in each section.  Minimum bus bracing is 65,000 amperes RMS symmetrical.  Higher symmetrical bracings are available based on the highest breaker short circuit rating in the group.

Load side run-backs for feeder circuits are one-piece copper construction.  Run-backs are insulated with sleeve tubing in the main bus area and supported by high strength, glass polyester moldings.

Assembly Construction

The metal-enclosed power switchgear is constructed of preformed, full-depth, 14 gauge steel sheets bolted together and reinforced with cross-member braces to form a rigid, self-supporting compact assembly.  The top and rear plates, and side sheets are all 14 gauge steel.  When two vertical sections are mounted together, two sheets of 14 gauge steel separate adjacent circuit breaker compartments.

Bolted steel-glass polyester compartments housing each power circuit breaker are mounted in the vertical section to form the switchgear assembly.  This assembly isolates the circuit breakers from the bus/cable section and from adjacent circuit breaker compartments.

The bus/cable section includes the main horizontal bus, riser bus, connections from the main bus to each set of primary disconnects, and load side copper run-back bus.  The cable lugs are accessible without reaching over the main bus.  Grounded metal barriers can be provided to isolate the main bus from the cable connections.  Barriers are also available to isolate the incoming line of the main circuit breakers from the main load bus of the switchgear.

Control Wiring

Standard secondary and control wiring is #14 AWG extra-flexible, stranded copper type SIS.  Terminations are made with compression-type, insulated terminals.

For devices not having screw-type terminals, locking spade-type lugs are used.  Sleeve-type computer generated wire markers are provided as standard on each end of all control wires.

Insulation

The insulation used in the switchgear is fiberglass-reinforced, polyester material that has high impact strength and low moisture absorption.  Other features include high flame retardance, high resistance to chemical fumes, and long life at high temperatures.

Circuit Breaker Compartments

Typical circuit breaker compartments include primary disconnects, ground disconnect, drawout rails, and associated safety interlocks and secondary disconnects, if appropriate.  Compartments for electrically operated circuit breakers include secondary disconnects and control circuit fuses.  The pullout fuse holder has a set of clips to store the holder in the fuse block when the circuit is disconnected.  Up to three current transformers for metering or relaying can be mounted in each compartment.

Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices.  A typical compliment of devices includes a breaker control switch with red & green light, ammeter with switch, and test block.

Metering and Auxiliary Compartments

Metering and auxiliary compartments are available to house devices such as voltage transformers, metering, control power transformers, and supervisory devices that do not fit on a normal breaker door.

Instrument and Control Transformers

Voltage transformers and control power transformers are mounted  in auxiliary compartments.  These transformers are protected by primary pull-out type current-limiting fuses and secondary fuses.

Current transformers are normally mounted on the compartment primary disconnect studs where they are readily accessible.

Accessories

Each switchgear assembly includes the following standard accessories:

  • Handle for circuit breaker racking
  • Lifting bar assembly for all circuit breaker types
  • Spring charging handle for electrically operated circuit breakers
  • Container of touch-up paint

As an optional accessory, a test cabinet is available for indoor use that is wall mounted with necessary equipment for testing electrically operated breakers that have been removed from the breaker compartment.

Outdoor Switchgear

CP's outdoor switchgear is enclosed in a weather resistant (NEMA 3R) steel housing.  All exterior doors extend below the floor line and re sealed with synthetic rubber gaskets.

For protection from snow, rain, and dust, the switchgear rests on a six-inch, formed steel base, which provides rigid support and a tight bottom seal.  A heavy duty, coal tar emulsion protective undercoating 1/32 inch thick is applied to the underside for protection against moisture and corrosion.  Shielded ventilation housing permit proper air circulation while excluding dust, dirt, and foreign matter.  The full-length front doors are hinged and may be padlocked.  Rear doors are hinged and secured with captive bolts.

A lighted, unobstructive service aisle is provided at the front of the switchgear allowing inspection and maintenance without exposure to the elements.  An access door equipped with an emergency bar release is at each end of the aisle.  A GFI convenience outlet is included. 

Climatized substation buildings

As with all of CP manufactured equipment, low voltage switchgear can be mounted in one of our Power Control Centers and integrated with other power distribution equipment.


AC SWITCHGEAR
480 V Switchgear
5 kV Switchgear

15 kV Switchgear
27 kV Switchgear
38 kV Switchgear
RetroFitting

DC SWITCHGEAR
D.C. Switchgear
RetroFitting


INDEX | CORPORATE | PRODUCTS | ENGINEERING | SALES | CONTACT
CIRCUIT BREAKERS | SWITCHGEAR | CUSTOM FABRICATION
TRACTION POWER | FIELD SERVICE


Copyright © 2000-2005 Controlled Power, LLC. All Rights Reserved.