F B K     B R E A K E R     R A T I N G S

Type Tests carried out at 1000 volts exceeds the requirements of ANSI C37-16:1980 table 11A. As applications having longer time constants develop, proving tests are being performed using the special equipment necessary.

Circuit Breaker Size 4000 6000 8000 10000 12000
Continuous Current Rating Max (A) 4000 6000 8000 10000 12000
Voltage Rating (V) 800 800 800 800 800
Short Circuit Rating - Peak (kA Prospective) 200 200 200 200 200
Sustained (kA) 120 120 120 120 120
Short Time Withstand Current Ratings - 250ms 80 80 125 125 125
Overload Current Setting Range (kA) 4-16 6-24 8-32 10-40 12-48
Control Voltage (VDC) (Other Ratings Available) 125 125 125 125 125
Close Coil - Operating Voltage Range (VDC) 90-140 90-140 90-140 90-140 90-140
Close Coil - Current Average at 125VDC (A) 3.0 3.0 3.0 3.0 3.0
Trip Coil - Operating Voltage Range (VDC) 70-140 70-140 70-140 70-140 70-140
Close Coil - Current Average at 125VDC (A) 2.0 2.0 2.0 2.0 2.0